Welcome to Ivy Metering!

EM613001

1. Brief IntroductionEM613001 is a DC measuring device sampling by shunt. Support RS485 communication and upload data to the system platform through the communication between RS485 and concentrator (E...

DC measuring meter
  • DC measuring meter
4
  • Product Details
  • 1. Brief Introduction

    EM613001 is a DC measuring device sampling by shunt. Support RS485 communication and upload data to the system platform through the communication between RS485 and concentrator (EM613002 - its NB concentrator which allows 25 pcs of RS485 DC meters). Current platform supports simple reading and parameters setting,we advise customer have a system as per application, and we recommend simple reading with matched PC software. Din rail installation, with good reliability, small volume, beautiful appearance, easy installation and other characteristics.

     

    2. Technical Parameter

    Ref. voltage

    DC40V-400V

    Ref. current

    10~240A

    Impulse constant

    100imp/kWh

    LCD display

    LCD6+2

    Operation temp.

    -20~+70℃

    Average humidity

    75%

    Relative humidity

    95%

    Accuracy class

    Cl.1

    Communication

    RS485, communication protocol DLT645

    Power consumption

    0.4W,8VA

    Standard compliant

    GB/T 17708-2017 Static DC Energy Meter

    Accuracy Error of Cl.1 Meter

    Current value

    Limit of percentage error of Cl.1 meter

    0.05Ib≤I<0.1Ib

    ±1.5

    0.1Ib≤I<Imax

    ±1.0

     

    3. Function Description

       3.1 Metering Function

    DC measuring device sampling by shunt with high accuracy, which can measure DC energy, current,voltage.

     

    3.2 Communication Function

    Supports RS485 communication with protocol DTL645, which allows parameters setting and read or write power data.

    Upgrade locally through RS485.

     

    3.3 Display Function

    LCD will show: DC energy, current, voltage, tariff etc

    Support automatic scrolling display (interval 5S) and manual display

    Backlight display, press the page button to activate the backlight and read in dark condition.

     

    3.4 Others

    Alarming: alarming when over-voltage, under-voltage, over-current, threshold is settable.

    Tariff: 4 tariffs with 8 time slots.

    Event log: record of last 20 times of over-voltage, under-voltage,over-current events.